6. Other parameters

Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes. Modify
parameter settings as required. See Section 11, Table of extended parameters.
6.1

Input/output parameters

6.1.1
Low-speed signal
 : Low-speed signal output frequency
• Function
When the output frequency exceeds the setting of  an ON signal will be generated. This signal
can be used as an electromagnetic brake excitation/release signal.
This signal can also be used as an operation signal when  is set to 0.0Hz, because an ON
signal is put out if the output frequency exceeds 0.0Hz.
Output from the open collector output terminal OUT. (Default)
Output from relay output FLA-FLB-FLC is possible depending on the parameter settings.
[Parameter setting]
Title

Function
Low-speed signal output frequency
Output frequency
[Hz]
Set frequency

Low-speed signal output
Between OUT-NO terminals
Low-speed signal output:
Inverted
F-1
Adjustment range
0.0 ∼  (Hz)
0
E6581595
6
Default setting
0.0
Time [s]
ON
OFF
ON
OFF