3)
Using other speed commands with preset-speed command
Command mode selection

0: Terminal board
Frequency setting
VI
mode selection 
5: External contact
UP/DOWN
Active
Preset-speed
command
Terminal
Inactive
command valid
Note)
The preset-speed command is always given priority when other speed commands are input at the
same time.
An example of three-speed operation with the default settings is shown below. (Frequency settings are required for
 to  )
Output frequency
[Hz]
F-CC
S1(SS1)-CC
S2(SS2)-CC
0: Terminal board
1: Setting dial 1
(press in center to
save)
3: RS485
2: Setting dial 2
(save even if
power is off)
Preset-speed command valid Note)
Setting dial
command valid



0
Example of 3-speed operation
C-23
1: Panel keypad (including remote keypad),
0: Terminal block
VI
communication
5: External contact
UP/DOWN
Terminal
command valid
Communication
(The inverter doesn't accept Preset-speed command.)
command valid
Time
[s]
ON
OFF
ON
OFF
ON
OFF
E6581595
2: RS485 communication
1: Setting dial
(press in center
3: RS485
to record)
communication
2: Setting dial
Setting dial
Communication
command valid
command valid
3