Toshiba VFNC3-2001P Instruction Manual page 29

Industrial inverter
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
Remedies:
1.If there is no radio-frequency interference or similar problem, detach the built-in noise filter
capacitor, using the grounding capacitor disconnecting switch. (See 1.3.3-2))
2.Reduce PWM carrier frequency.
The setting of PWM carrier frequency is done with the parameter  .
Although the electromagnetic noise level is reduced, the motor acoustic noise is increased.
3. Use high frequency remedial products for earth leakage breakers
(3) Affects of leakage current across lines
Power
supply
Leakage current path across wires
(1)
Thermal relays
The high frequency component of current leaking into electrostatic capacity between inverter out-
put wires will increase the effective current values and make externally connected thermal relays
operate improperly. If the wires are more than 50 meters long, it will be easy for the external
thermal relay to operate improperly with models having motors of low rated current (several
A(ampere) or less), because the leakage current will increase in proportion to the motor rating.
Remedies:
1.Use the electronic thermal built into the inverter. (See 3.5)
The setting of the electronic thermal is done using parameter  ,  .
2.Reduce the inverter's PWM carrier frequency. However, that will increase the motor's magnetic
noise.
The setting of PWM carrier frequency is done with the parameter  . (See 6.11 in E6581595)
3.This can be improved by installing 0.1µ~0.5µF - 1000V film capacitor to the input/output terminals of
each phase in the thermal relay.
Thermal relays
CT
Inverter
A
U/T1
V/T2
W/T3
Thermal relays
A-17
E6581595
IM
IM
1

Advertisement

Table of Contents
loading