Toshiba VFNC3-2001P Instruction Manual page 233

Industrial inverter
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
[Alarm information]
Error code






/

/











13


Note) When the ON/OFF function is selected for DC braking (DB), using the input terminal selection parameter, you can judge
the inverter to be normal if "" disappears when opening the circuit between the terminal and CC.
Each message in the table is displayed to give a warning but does not cause the inverter to
trip.
Problem
• The ST-CC circuit is opened.
ST terminal OFF
• The supply voltage between R, S and T is
Undervoltage in main
circuit
under voltage.
Retry in process
• The inverter is n the process of retry.
• A momentary stop occurred.
Frequency point
• The frequency setting signals at points 1
setting error alarm
and 2 are set too close to each other.
Clear command
• This message is displayed when pressing
acceptable
the STOP key while an error code is
displayed.
Emergency stop
• The operation panel is used to stop the
command acceptable
operation in automatic control or remote
control mode.
• An error is found in a setting when data is
Setting error alarm /
An error code and
reading or writing.
data are displayed
alternately twice
each.
Display of first/last
• The first and last data item in the 
data items
data group is displayed.
DC braking
• DC braking in process
Flowing out of
• The number of digits such as frequencies
excess number of
is more than 4.
digits
(The upper digits have a priority.)
Momentary power
• The slowdown stop prohibition function
failure slowdown
set with  (momentary power
stop prohibition
failure ride-through operation) is
function activated.
activated.
Auto-stop because of
• The automatic stop function selected with
continuous operation
 was activated.
at the lower-limit
frequency
Parameters in the
• Parameters are being initialized to default
process of
values.
initialization
Output frequency
• An attempt was made to operate at a
upper limit
frequency higher than 10 times the base
frequency ( or ).
Operation panel key
• The RUN or STOP key is held down for
fault
more than 20 seconds.
• The RUN or STOP key is faulty.
Auto-tuning
• Auto-tuning in process
Source logic
• The input terminal was switched to source
switching check
logic.
alarm
Sink logic switching
• The input terminal was switched to sink
check alarm
logic.
Possible causes
• Close the ST-CC circuit.
• Measure the main circuit supply voltage.
• The inverter is normal if it restarts after
• Set the frequency setting signals at points
• Press the STOP key again to clear the
• Press the STOP key for an emergency
• Check whether the setting is made
• Press MODE key to exit the data group.
• The message goes off in several tens of
• Lower the fequency free unit
• To restart operation, reset the inverter or
• To deactivate the automatic stop function,
• Normal if the message disappears after a
• Operate at a frequency within 10 times
• Check the operation panel.
• Normal if it the message disappears after
• Check the wiring, and set the appropriate
• Check to make sure that the wiring is
M-4
E6581595
Remedies
If the voltage is at a normal level, the
inverter requires repairing.
several tens of senconds.
The inverter restarts automatically. Be
careful of the machine because it may
suddenly restart.
1 and 2 apart from each other.
trip.
stop.
To cancel the emergency stop, press any
other key.
correctly.
seconds if no problem occurs. Note)
magnification .
input an operation signal again.
increase the frequency command above
the lower-limit frequency (LL) + 0.2 Hz or
turn off the operation command.
while (several seconds to several tens of
seconds).
the base frequency.
a few seconds.
logic.
normal, and reset or turn the power off
and then back on again. This switches the
logic.