Toshiba VFNC3-2001P Instruction Manual page 232

Industrial inverter
Table of Contents

Advertisement

efesotomasyon.com -Toshiba inverter,drive,servo,plc
(Continued)
Error code
Failure code

0011

0012

0013
0014


0015

0016

0017

0018

001A
001D
*

001E
*


0022

0054

0029
0032
*


0033

0034

0035

003A
*
You can select a trip ON/OFF by parameters.
Problem
• During automatic operation or remote
Emergency stop
operation, a stop command is entered
from the operation panel or a remote
input device.
EEPROM fault 1
• A data writing error occurs.
EEPROM fault 2
• Power supply is cut off during 
operation and data writing is aborted.
EEPROM fault 3
• A data reading error occurred.
Main unit RAM fault
• The control RAM is defective.
• The control ROM is defective.
Main unit ROM fault
CPU fault 1
• The control CPU is defective.
Remote control error
• An error arises during remote operation.
Current detector fault
• The current detector is defective.
Low-current
• The output current decreased to a low-
operation
current detection level during operation.
Trip
Undervoltage trip
• The input voltage (in the main circuit) is
(main circuit)
too low.
Ground fault trip
• A ground fault occurs in the output cable
or the motor.
Auto-tuning error
• Check the motor parameters , , , , , , and
.
• The motor with the capacity of 2 classes or less than the inverter is used.
• The output cable is too thin.
• The motor is rotating.
• The inverter is used for loads other than those of three-phase induction motors.
Inverter
• Circuit board is changed.
type error
(Or main circuit/drive circuit board)
Brea in analog signal
• The input signal from VI is equal to or less
cable
than the  setting.
CPU
• A communications error occurs between
communications
control CPUs.
error
Excessive torque
• The automatic torque boost parameter
boosted
 setting is too high.
• The motor has too small impedance.
CPU fault 2
• The control CPU is defective.
CPU fault 3
• The control CPU is defective.
Possible causes
• Reset the inverter.
• Turn off the inverter, then turn it again. If it
• Turn the power off temporarily and turn it
• Turn off the inverter, then turn it again. If it
• Make a service call.
• Make a service call.
• Make a service call.
• Check the remote control device, cables,
• Make a service call.
• Enable  (low-current detection).
• Check the suitable detection level for the
• Make a service call if the setting is
• Check the input voltage.
• Enable  (undervoltage trip
• To cope with a momentary stop due to
• Check the cable and the motor for ground
• Make a service call.
• Check the VI signal cable for breaks.
• Make a service call.
• Set a lower automatic torque boost
• Make a service call.
• Make a service call.
M-3
E6581595
Remedies
does not recover from the error, make a
service call.
back on, and then try  operation
again.
does not recover from the error, make a
service call.
etc.
system (, , ).
correct.
selection).
undervoltage, enable  (ride-
through control) and  (auto-
restart).
faults.
Also, check the input signal value or
setting of .
parameter  setting.