Output Frequency Detection; Output Current Detection Function - Mitsubishi Electric FR-CS82S-025 Instruction Manual

Hide thumbs Also See for FR-CS82S-025:
Table of Contents

Advertisement

• The following is the list of faults that output the Y91 signal. (For the fault details, refer to
Fault record
Inrush current limit circuit fault (E.IOH)
CPU fault (E.CPU)
Parameter storage device fault (E.PE)
Parameter storage device fault (E.PE2)
Output side earth (ground) fault overcurrent (E.GF)
Output phase loss (E.LF)
Parameters referred to
page 99
Pr.13 Starting frequency
5.7.3

Output frequency detection

If the inverter output frequency which reaches a specific value is detected, the relative signal is output.
Pr.
Name
41
Up-to-frequency
M441
sensitivity
42
Output frequency
M442
detection
Output frequency
43
detection for reverse
M443
rotation
 Setting the notification zone of the output frequency reaching the set
point (SU signal, Pr.41)
• The Up to frequency (SU) signal is output when the output frequency reaches the set frequency.
• The
value can be adjusted within the range ±1% to ±100% considering the set frequency as 100%.
Pr.41
• It may be useful to use this signal to start operating related equipment after checking that the set frequency has been
reached.
Set frequency
OFF
OFF
ON
SU
Parameters referred to
Pr.195 (Output terminal function selection)
5.7.4

Output current detection function

If the inverter output current which reaches a specific value is detected during operation, the relative signal is output via an
output terminal.
Pr.
Name
150
Output current detection
M460
level
151
Output current detection
M461
signal delay time
167
Output current detection
M464
operation selection
 Output current detection (Y12 signal, Pr.150, Pr.151, Pr.167)
• The output current detection function is useful for overtorque detection.
Setting
Initial value
range
10%
0 to 100%
6 Hz
0 to 400 Hz
0 to 400 Hz
9999
9999
Adjustment
range Pr.41
Time
page 126
Initial
Setting range
value
150%
0 to 400%
0 s
0 to 10 s
0
0, 1
page
Description
Set the level where the SU signal turns ON.
Set the frequency at which the FU signal turns ON.
Set the frequency at which the FU signal turns ON only while the
motor rotates in reverse direction.
Same as the Pr.42 setting.
Description
Set the output current detection level. Consider the value of the
rated inverter current as 100%.
Set the output current detection time. Enter the delay time
between the time when the output current reaches the set
current or higher and the time when the Output current
detection (Y12) signal is output.
Select the inverter operation at the time when the Y12 signal
turns ON.
5.7 (M) Item and output signal for monitoring
211.)
129
5. PARAMETERS