Pump Control; Alarm - Xylem FLYGT Pareo DCM 711 Installation, Operation And Maintenance Manual

Control module
Table of Contents

Advertisement

8.4.2 Pump control

Part
Pump name
Site name
Start condition
Stop condition
Snoring sensitivity
Level settings
Minimum pause
time
Maximum pause
time
Reference power
Correct the rotation –

8.4.3 Alarm

Alarm
Service alarm
DCM 711 Installation, Operation, and Maintenance Manual
Default value
Values
Four or more
characters
Four or more
characters
Timer
• Timer
• Float
• Timer/Float
Snore
• Snore
• Float
0.86
0–1
1
1–10
25 s
1–999 s
90 s
1–999 s
According to the
information from
the pump module
Default value
Enabled
Description
The option to change the name of the
pump
The option to change the name of the
site
The selection of the start condition of the
automatic control mode
The selection of the stop condition of the
automatic control mode
Only the stop conditions that are
applicable for the configured start
condition are shown.
Low value
The snoring
sensitivity is low.
Snoring is detected
at high air volumes
in the fluid.
The value of the Level settings
parameter is used to calculate the pause
time. The parameter does not define the
water level in the well.
The minimum time that the pump is on
standby
The maximum time that the pump is on
standby
The value of the reference power
The controller uses the reference power
of the pump to detect snoring.
There are three options to set the
reference power:
• Reference power
• Calibrate the reference power
• Reset reference power
For more information, see
reference power
on page 26.
The option to switch the pump rotation
Used when the pump has been
miswired.
The option can only be used in standard
mode.
Values
Description
• Disabled
• Disabled
• Enabled
• Enabled
8 User Interface
High value
The snoring
sensitivity is high.
Snoring is detected
at low air volumes
in the fluid.
Set the
The alarm is disabled.
The alarm is enabled.
39