Download Print this page

Input And Output Functions (Control Terminals) - Xylem Aquavar SPD SPD20050 Instruction Manual

Variable speed pump control

Advertisement

Available languages

Available languages

INPUT AND OUTPUT FUNCTIONS
Section 8
of a non-powered external switch to terminals 3 (COM) and 4 (HAND/AUTO). When the switch is closed the
controller is in HAND mode. While in HAND mode the RUN/STOP input is used to start and stop the motor and
the pressure transducer input is ignored. When the switch is open the controller is in AUTO mode. While in
AUTO mode the controller uses the pressure transducer feedback to control the speed of the motor.
INPUT and +24V: These terminals are the transducer feedback and transducer power supply. Connect the
white lead from the transducer cable to terminal 6 (INPUT). Connect the brown lead from the transducer cable to
terminal 7 (+24V). Connecting the drain (bare) wire to the chassis allows grounding of the case of the pressure
transducer. The controller is configured with a 300 PSI 4-20mA output pressure transducer.
ANALOG OUTPUT: This output is a 4-20mA signal based on motor speed (4mA = 0Hz, 20mA = 60Hz) and can
be connected to external monitoring or external control devices. Connect terminal 10 (ANALOG OUTPUT) to the
4-20mA input of the external device. Connect terminal 9 (COM) to the negative side of the current loop on the
external device. The external device must have an input resistance (impedance) in the range of 45Ω to 250Ω. The
maximum output voltage is 24V.
SP2/SP1: This input allows the system to operate at one of 2 pressure settings. This input can be controlled by
an external non-powered switch. Connect the contacts of a non-powered external switch to terminals 5 (COM)
and 11 (SP2/SP1). When the switch is closed pressure set point 2 is enabled (preset to 75 PSI when used with a
300 PSI transducer). When the switch is open pressure set point 1 is enabled (preset to 50 PSI when used with a
300 PSI transducer).
PRESSURE DROP: This input allows the user to select the amount of pressure drop in the system before the
pump starts. This input can be controlled by an external non-powered switch. Connect the contacts of a non-
powered external switch to terminals 5 or 9 (COM) and 12 (PRESSURE DROP). When the switch is closed the
system pressure will drop 20 PSI (when used with a 300 PSI transducer) before restarting the pump. When the
switch is open the system pressure will drop 5 PSI (when used with a 300 PSI transducer) before restarting the
pump.
RUN RELAY: This output indicates when the pump/motor is running. This output can be used to control power
to a light, an alarm or other external device. When the pump/motor is off terminal 13 (RELAY1 – NO) will be open
and terminal 14 (RELAY 1 – NC) will be connected to terminal 15 (RELAY1 – COM). When the pump/motor is on
terminal 13 (RELAY1 – NO) will be connected to terminal 15 (RELAY1 – COM) and terminal 14 (RELAY 1 – NC) will
be open. The relay rating is 250Vac, 5 amps maximum.
FAULT RELAY: This output indicates when the system is faulted. This output can be used to control power to a
light, an alarm or other external device. When the system is not faulted terminal 16 (RELAY2 – NO) will be open
and terminal 17 (RELAY 2 – NC) will be connected to terminal 18 (RELAY2 – COM). When the system is faulted
terminal 16 (RELAY2 – NO) will be connected to terminal 18 (RELAY2 – COM) and terminal 17 (RELAY 2 – NC) will
be open. The relay rating is 250Vac, 5 amps maximum.
The control terminal strips allow for a variety of input and output functions.
Warning: Turn off all power to the controller before wiring devices to the
control terminals.
Warning: Inputs RUN/STOP, HAND/AUTO, SP2/SP1 and PRESSURE DROP
are switch inputs. Do not connect power to these inputs or damage to the
controller will result. Only connect non-powered switch contacts to these
inputs.
RUN/STOP: This input allows the pump/motor to be turned on and off by
an external switch. Connect the contacts of a non-powered external switch
to terminals 1 (COM) and 2 (RUN/STOP). When the switch is closed the
controller is in RUN mode (output to motor is enabled). When the switch is
open the controller is in STOP mode (output to motor is disabled).
HAND/AUTO: This input allows the controller to run the motor at
full speed without the use of a pressure transducer. This input can be
controlled by an external non-powered switch. Connect the contacts
Page 19

Hide quick links:

Advertisement

Chapters

loading