3 Function Description
Alarm
Phase imbalance,
pump current
Phase imbalance,
voltage
Pump
communication
failure
Pump leakage
Pump short circuit
Pump thermal
alarm
Pump thermal
warning
Service alarm
Startup failure
Undercurrent
Undervoltage
16
Possible cause
Remedy
There is a current
Check the wiring
imbalance in the
and the
phase leads of the
connections to the
pump.
terminals.
There is a voltage
imbalance in the
connections to the
controller.
There is no
Check the wiring
communication
and the
between the
connections to the
controller and the
terminals.
pump.
There is a leakage
Examine and repair
in the pump.
the leakage.
There is a short
circuit in the signals
from the FLS
sensor.
The thermal
Check the pump
sensors detect that
temperature.
the temperature is
higher than the
permitted limit.
The thermal
Check the pump
sensors detect that
temperature.
the temperature is
high.
The pump is due
for service.
The controller
Upgrade the
cannot start
software of the
correctly.
controller.
The pump does not
• Check the
receive sufficient
incoming power
voltage.
supply.
• Check the wiring
and the
connections to
the terminals.
The pump does not
• Check the
receive sufficient
incoming power
voltage.
supply.
• Check the wiring
and the
connections to
the terminals.
DCM 711 Installation, Operation, and Maintenance Manual
Priority level
Reset
Class A
Automatic
Class A
Manual
Class B
Automatic
Class A
Automatic
Class A
Automatic
Class A
Automatic
Class B
Automatic
Class B
Manual
For more
information, see
Reset the service
alarm
on page 25.
Class A
Manual
Class A
Automatic
Class A
Automatic