5 System Setup and Operation

5.3.8 Set the reference power

The controller uses the reference power of the pump to detect snoring. If the reference
power is not known, then the parameter is configured in the Settings menu.
Set the reference power.
Condition
Use of the default
reference power.
Calibration of the
reference power.
Manual set of the
reference power.
26
Action
1. Go to Settings > Pump control > Reference power > Reset reference
power.
2. Confirm.
1. Check that there is water in the well.
2. Press the HAND button.
3. Go to Settings > Pump control > Reference power > Calibrate the
reference power.
4. Confirm the initialization of the calibration.
1. Go to Settings > Pump control > Reference power > Reference power.
2. Type the value.
DCM 711 Installation, Operation, and Maintenance Manual