Supplementary Information; Periphery Devices - Teletek electronics iRIS8 Installation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

iRIS8 - Addressable Fire Alarm Panel – Installation Manual

5. SUPPLEMENTARY INFORMATION

5.1. Periphery Devices

All "functional modules" connected to the control panel configuration are defined as Periphery Devices, and have
special programming and settings.
Attention: The Interface module and Main control module PCB are not periphery devices!
Up to 12 periphery devices can be added to the system configuration of iRIS8 panel. The number and type of the
functional modules depend on the panel's model.
Periphery Device
System name and description
PSU – Main power supply
OUT – Outputs module
LOOP – Loop controller (expander)
The periphery devices have factory set address numbers that cannot be changed. The following diagram shows the
position and the set factory addresses. The loop controllers always take addresses from 3 to 10.
The following drawing of the hardware configuration of iRIS8 panel models and table represent the fixed factory
addresses of the periphery devices, which must be assumed during the initial power up and programming of the whole
system.
Model and max. number of supported periphery devices
iRIS8 S
iRIS8 S + iRIS8 Ext
1
1
4
Model
iRIS8
The free addresses for periphery devices are
presented as EMPTY.
Figure 38
30
iRIS8 B
2
2
2
2
8
8
System
Periphery
Name
Device
PSU
PSU 1
OUT
OUT 1
LOOP
LOOP 1
LOOP
LOOP 2
LOOP
LOOP 3
LOOP
LOOP 4
LOOP
LOOP 5
LOOP
LOOP 6
LOOP
LOOP 7
LOOP
LOOP 8
PSU
PSU 2
OUT
OUT 2
Factory
Address
1
2
3
4
5
6
7
8
9
10
11
12