Permissible Cable Length - Teletek electronics iRIS8 Installation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

4.5.1 Permissible Cable Length

The maximum length of the loop in the system could vary according to the cross-section and the ohmic resistance of the
used cable.
Nevertheless, there is no specific requirement for cable description according to standard EN 54-2, the manufacturer
recommends using the listed cables in installations:
No
Brand
1
Mining Ltd Fire cable AF*
BERICA CAVI S.P.A ITALY
2
MULTICORE FLEX SCR
TEKAB FireTEK, SA7Z1,
3
ZA7Z1, MZA7Z1
4
Atron ACFF
5
Atron ACFR
6
Atron PIROFREN SOZ1-K
*This cable is tested and approved.
ATTENTION: iRIS8 TTE loop controller supports up to 250 devices!
To ensure the correct operation of the system is necessary to make some calculations in advance:
1. To ensure the ability of the fire
panel to receive the signals from the
devices in the loop, calculate:
≤ 123 / R
L
C1max
Where:
L
, L
and L
C1MAX
C2MAX
C3MAX
R
- is total ohmic resistance of the two wires of the used able; its value shows the magnitude of the cable resistance at
C
length 1km [Ω/km];
R
- is the total resistance of the isolator modules in the loop;
I
I
- is the maximum current consumption in the loop in alarm condition - total amount of the current consumption of all
max
devices in alarm state** in the loop.
Note: In case of using more than 15 devices SensoIRIS series from type T110/ T110 IS, S130/ S130IS, M140/ M140IS,
MCP150 and MC-Z, in calculation of I
15 devices with the highest consumption, and for the rest devices is used the consumption in stand-by mode**.
** For the max. current consumption in alarm state and the consumption in quiescent state with communication (stand-by mode) of a device refer to its
installation manual.
L
- is the necessary length of the cable for the loop.
C
After calculating, the maximal length of the cable is determined according:
·
≤ L
If L
and L
C
C2max
C
be able to identify the presence of double address.
·
≤ L
If L
< L
C2max
C
C1max
will not be able to identify the presence of double addresses.
ATTENTION: Always calculate the maximal cable length according the mentioned above formulas!
IF L
> L
or L
> L
C
C1max
C
C3max
Parameters
Unscreened, CEI 20/22 II IEC 60332-3, GR2, C-4 (U0=400V) CEI-UNEL-36762,
2x0.8mm
2
Screened, CEI 20/22 II CEI EN 60332-1-2, CL 5 CEI EN 60228 VDE 0295,
300/500V, 2x0.5/0.75/1.0/1.5mm
Screened, C/W BS 6387, Class-1/Class-2 BS 6360, 300/500V, 2x1.0/1.5/2.5mm
Screened, IEC332,2, 2x1.0/1.5/2.5mm
Screened, IEC332,2, 2x0.8mm
Screened, PH90 DIN EN 50200 TS IEC 60331-2, 300/500V, 2x0.8/1.5mm
2. To ensure the ability of the fire
panel to recognize the double
addresses in the system, calculate:
C
- are maximum permissible length of the used cable, [km];
value is used the maximum current consumption in alarm state** only for those
max
≤ L
- the fire panel will be able to communicate with the devices in the loop and also will
C3max
≤ L
and L
- the fire panel will be able to communicate with the devices in the loop but
C
C3max
- the fire panel would not be able to communicate with the devices.
iRIS8 - Addressable Fire Alarm Panel – Installation Manual
2
2
≤ 62 / R
L
C2max
C
21
2
3. To ensure the ability of the devices
in the loop to receive command
signals from the panel, calculate:
≤ (12 / I
L
C3max
2
2
- R
) / R
max
i
C

Advertisement

Table of Contents
loading

Table of Contents