iRIS8 - Addressable Fire Alarm Panel – Installation Manual
For the correct operation of the system configuration with iRIS8 panel, is obligatory also to set the DIP switches and
jumpers of the FAT indication panel and SM3 redundancy module in the following way:
FAT Panel
SM3 Module
DIP Switches
Jumper Settings
DIP Switches
Jumper Settings
Note: The detailed description and documentation for FAT-KÜ control panel, SM3-RM module and other suitable
products is available at the site of the manufacturer -
https://www.schraner.de
General Description
The performed above configuration of iRIS8 and FAT/FBF control panel is realized at the protected site. In case of a fire
alarm situation the dialer sends an alarm signal to the Fire Brigade Unit. The Fire Brigade Unit receives the signal and
confirms it (via a special switch installed at Fire Brigade Site, according German standards*). The iRIS8 panel receives
the signal from the Fire Brigade and unlocks the adapter box with key safe. (The key safe keeps all the keys for the
rooms in the protected site.) The Fire Brigade Officer unlocks the key safe (with own key) and takes all the keys for the
rooms. When the fire is extinguished, the Fire Brigade Officer returns all the keys back to the key safe and locks it. Now
the iRIS8 panel must be reset to normal operation mode. After resetting, the adapter of the key safe is locked, the Dialer
is returned to stand-by mode, and all of the messages for alarms and warnings are cleared.
* For detailed information about the system requirements according the German standards and the operation of iRIS8
panel connected to FAT/FBF (Fire Brigade Indication and Operation Panel) you can ask your distributor.

4.6.4. PASO Panels Connection

The addressable fire alarm panel iRIS8 is designed with option for connection to PASO specialized panels for voice
evacuation and/or sound management systems. The PASO panels are connected to iRIS8 panel via RJ1 terminal of the
interface module (Figure 27, position 7).
To use the Evacuation Voice system, the installer must program a number of parameters in menu (access level 3):
System-Programming-Panel-Sounders Mode-MORE-Evac Zones.
The communication is based on RS485 interface.
Attention: Connection of max. 6 panels, numbered from 0 to 5, in a network (5 PASO panels and 1 iRIS8 panel)!
iRIS8 panel always takes the last number in a network with PASO panels!
iRIS8 Panel #5
(Interface module)
Figure 31