Working Environment; Weight And Dimensions; Electrical Characteristics - Teletek electronics iRIS8 Installation Manual

Addressable fire alarm control panel
Table of Contents

Advertisement

1.3.2 Working Environment

IP30
Operation temperature: -5ºС up to +40ºC
Relative humidity: up to 95% (without condense)
Storage temperature: -10ºС up to +50ºC

1.3.3 Weight and Dimensions

Weight (without battery/batteries):
iRIS8 B
~15 kg
Dimensions:
iRIS8 B
430x660x120 mm

1.3.4 Electrical Characteristics

Cable: 4-wire
Cross section: 0.25mm
Up to 1000m long distance
Earth Connection
The earth connection has to be realized in accordance with the rules for the electrical safety with the total resistance in
the circuit lower than 10Ω. It is mandatory to connect the main power supply cable to the middle input of the fire panel
terminal – see also item
Main power supply
In normal operating conditions the fire panel is powered from the mains voltage line. In case of mains voltage line loss
the fire panel is designed to operate with back-up power supply – one or two batteries according the model. The
characteristics of the main power supply are as follows:
Main Power Supply: ........................................................... 110÷230VAC
Frequency: ......................................................................... 50/ 60Hz
Electrical output:
o
For 4 loops connected........................................... ~15A
o
For 8 loops connected........................................... ~30A
Backup Battery Power Supply
Current output (I): ............................................................... max. 20A
Internal resistance of the accumulator battery Ri............... < 0.3 Ohm
Number of Batteries:
o
iRIS8 B: ................................................................. 2 x 12V/ 18Ah
o
iRIS8 S and iRIS8 Ext ........................................... 1 x 12V/ 18Ah
Battery Size: ....................................................................... 167x181x76mm
Battery type: ....................................................................... rechargeable, sealed lead-acid type
Type of the Battery connection: ......................................... with a flat terminal lug - Ø5mm (M5)
Consumption
From the main power supply in standby mode:
For 1 loop configuration: .................................................... 65 mA AC
For 2 loops configuration: ................................................... 75 mA AC
For 3 loops configuration: ................................................... 85 mA AC
For 4 loops configuration: ................................................... 95 mA AC
From the backup power supply in FAULT mode and generated message "AC loss":
For 1 loop configuration: .................................................... 285 mA DC
For 2 loops configuration: ................................................... 360 mA DC
For 3 loops configuration: ................................................... 435 mA DC
For 4 loops configuration: ................................................... 510 mA DC
iRIS8 S
~7 kg
iRIS8 S
430x330x120 mm
2
4.1
Main Power Supply connection.
iRIS8 - Addressable Fire Alarm Panel – Installation Manual
iRIS8 Ext
~6 kg
iRIS8 Ext
430x330x120 mm
7