7.3.1 Measure input settings

In the 7.1 Measure configurations menu you can set the how
connect the device to network. Here you can set the voltage
and currents transformers for inputs (if they are usable) and
other special parameters of the measurement.

7.3.1.1. Measure configuration

The device can operate several types of measurement
setup. In the 7.1 Measure configurations menus you can
set the measuring arrangement. Possible measuring modes:
3 phase, 4 wire, 3 meter:
Three phase measurement with neutral conductor
3 phase, 3 wire, 3 meter:
Three phase measurement without neutral conductor
3 phase, 3 wire, 2 measure:
Three phase measurement without neutral conductor. Using
2 meter configuration. (Aron mode)
3 phase, 4 wire, 1 meter:
Three phase measurement with neutral conductor. Using 1
meter configuration. It is assumed symmetric load system,
so you can use the measurement of rotating electrical
machines.
3 phase, 3 wire, 1 meter:
Three phase measurement without neutral conductor. Using
1 meter configuration. It is assumed symmetric load system,
so you can use the measurement of rotating electrical
machines.
3 phase, 3 wire, 3 meter, 3fmv:
Three phase measurement without neutral conductor, and
threephase voltage transformers with delta secondary
winding. The secondary winding of the transformer is
connecting to earth. The Voltage transformers ratio is
multiplied √3!
You can find the electrical wiring diagrams for each
measurement arrangement on 5. Connecting chapter.