DT4220 E
Function
Sequence of operations Read the chapter 7.1. Functions of the push-buttons during
Function
Sequence of operations Read the chapter 7.1. Functions of the push-buttons during
20180619-V0
7.5. Menu item 01: Display brightness
The brightness can be set between 10%-100%, in 10% steps.
[factory default: 100%]
navigation in the menu for learning the buttons handle.
1. Enter the menu by typing the supervisor code.
2. Keep stepping by pressing the ▲ button as long as you see this
menu item.
3. Enter the menu item by pressing the Menu button.
4. Pressing the ▲ button, select the desired value.
5. Exit from menu item by pressing the Esc button. The change is
saved to FRAM.
(6. Press Esc button again if you want to leave the menu.)
The selectable values: 100, 90, 80, 70, 60, 50, 40, 30, 20, 10.
7.6. Menu item 02: Input selection
The instrument has current and voltage inputs. Here you can select
the input and the signal level.
[Factory default: 4-20 mA current input]
navigation in the menu for learning the buttons handle.
1. Enter the menu by typing the supervisor code.
2. Keep stepping by pressing the ▲ button as long as you see this
menu item.
3. Enter the menu item by pressing the Menu button.
4. Pressing the ▲ button, select the desired value.
5. Exit from menu item by pressing the Esc button. The change is
saved to FRAM.
(6. Press Esc button again if you want to leave the menu.)
The selectable values: I 4-20, I 0-20, U 0-10, U 0-5, U 2-10.
35