Datcon PQRM5300 33 U I Series Instruction Manual page 87

Three-phase power meter
Table of Contents

Advertisement

PQRM5300 33 Ux Ix xx xx (PS)
Output parameters:
The device has one analogue option or one communication option at same time.
MODBUS communication interface (optional):
RS485
Interface type:
Baud rate:
Parity:
Protocol:
Address:
Possible commands:
Termination:
Ethernet
Interface type:
Protocol:
Device address:
Commands:
Settings:
Analogue outputs (optional)
Output type:
Ranges:
Burden:
Refreshing time:
Setting time: (10-90%)
Overcurrent:
Error:
Burden resistance effect:
Pulse outputs (optional):
Output type:
Rating:
20201120-V1
RS485, galvanic isolated
300 / 600 / 1200 / 2400 / 4800 / 9600 /
14400 / 19200 / 32800 / 56000 / 57600 /
115200 Baud
even / odd / none
MODBUS RTU / ASCII slave
1-240
3 (register read)
16 (register write)
External (not part of device)
Ethernet 10/100 Base-T, galvanic isolated
MODBUS TCP/IP, server
1
3 (register read)
16 (register write)
IP address, Default gateway, Subnetwork
mask
Static IP address (DHCP not supported)
2 galvanic isolated active current outputs
(configurable, scalable)
0-20 mA / 4-20 mA or
0-5 mA / 1-5 mA
500 ohm (max.)
same as the measuring time (100 ms)
Max. 60 ms
20.8 mA
<4 uA (23 °C ±2 °C), <40 uA (-20 - 60 °C)
practically zero
2 galvanic isolated transistor
30 V, 50 mA
87