1. About this document 1.1. Function This operating instructions manual has all the information you need for quick set-up and safe operation of DT7000. Please read this manual before you start setup. 1.2. Target group This operating instructions manual is directed to trained personnel.
2.5. EU conformity The DT7000 is in conformity with the provisions of the following standards: MSZ EN 60079-0:2013 (ATEX) MSZ EN 60079-0:2013/A11:2014 (ATEX)
DT7000 2.6. Safety information for Ex areas Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the concerning standards of Ex-approved instruments. Warning! Electrostatic hazard. Clean the instrument housing with a moist cloth and detergent! 2.7.
For other requirements see: Chapter 9.1. Technical specification, Safety data. 3.3. Adjustment The DT7000 is calibrated for the ordered measuring range. If needed it is possible for the user to calibrate the instrument via the internal trimmer potentiometers. 3.4. Storage and transport...
If the displayed value is > 1 digit in case of open pressure ports you can adjust it according Chapter 6.1. Zeroing. The protection of the instrument is IP 65. Water, humidity In a case of using DT7000 outdoor mount a shield over the instrument to protect it against strong rain. 20171206-V1...
DT7000 4.3. Mounting procedure There are two through-holes (1), shown by arrows in the Mounting holes following figure, for fastening of the housing. The diameters of the holes are made for M4 screws. 1. Mark the places of the holes on the mounting surface in accordance with the drawing.
Page 12
DT7000 Mounting the instrument Two M4 threaded screws are needed for mounting the instrument (these are not accessories). The type of the screws depends on the wall-material, while the dimensions depend on the wall-thickness. The minimum screw-length should be the wall-thickness + 10 mm.
Selection power supply The DT7000 is a two-wire 4-20 mA transmitter. The supply voltage is 12-28 VDC. For other requirements see: Chapter 9.1. Technical specification, Safety data.
DT7000 5.2. Connection procedure The following figure shows the wiring plan connecting the transmitter: Wiring plan, connecting the transmitter (see also “Application example”) Be careful the polarity of the cables 1. Prepare the cable for connecting (see Figure 2.). 2. Loosen the screw in the cover of the cable socket connector and remove it.
DT7000 5.3. Connecting the pressure to the instrument Use pneumatic tube with 4 mm inner diameter for connecting the pressure. Simply push the tube ends onto the pressure connection stubs. There is no need any clamp under 50 mbar pressure.
DT7000 6. Setting up 6.1. Zeroing The DT7000 is calibrated according to the measuring range given on the data label. However a small zero offset may occur caused by the shock under shipping or mounting. This can be trim by potentiometers.
DT7000 6.2. Calibrate the instrument If necessary and if you have an adequate infrastructure for calibration you can calibrate the instrument. The calibration must be carried out by trained and authorized personnel only! First adjust the current output because it has an influence on the display value.
If the fault finding is not successful call the manufacturer service department. 7.2. Repairing There is no user repairable part inside the instrument. In accordance with Point 2.1.: For safety and warranty reasons, any internal work on the instrument must be carried out by DATCON personnel. 20171206-V1...
DT7000 8. Dismounting 8.1. Dismounting procedure 1. Disconnect the connector from the instrument (see chapter 5.2.). 2. Dismount the pressure tubes from the instrument (see Chapter 5.3.). 3. Remove the front cover (see Chapter 4.3.). 4. Remove the two fixing screws (see Chapter 4.3.).