Analogue Output Settings - Datcon PQRM5300 33 U I Series Instruction Manual

Three-phase power meter
Table of Contents

Advertisement

Function
Sequence of operations 1. Log in the 7. Configurations menu
60

7.4.2. Analogue output settings

There can be two optional dual independent analog outputs
of the instrument. Any of the measured quantities can be
transmit in a 0 / 4-20 mA current form.
Here you can set all of the parameters of the outputs.
Measured quantities are:
U
, U
, U
, U
, U
12
23
31
L1
P
, P
, P
, Q
, Q
L1
L1
L3
L1
PF
, PF
, PF
, φ
L1
L2
L3
ΣP, ΣQ, ΣS, ΣPF, Σφ, f
2. Choose the 7.2. Modul #2 settings menu of the
7. Configurations menu with  /  buttons, and press
the ENTE switch.
3. Choose the 7.3.1 A1 analog output menu of the 7.3.
Modul #2 settings menu with  /  buttons, and press
the ENTE switch.
4. Press the ENTE switch.
5. Choose the assign menu with  /  buttons, and
press the EDIT switch.
6. Select from the menu with  switch the measured
quantity what you are going to transmit.
7. Press the SEL switch.
8. Press the OK switch.
9. Choose the Range from menu with  /  buttons, and
press the EDIT switch.
10. Type the low value of the output scale with help  , - ,
+ switches, and press the OK switch to accept the value.
11. Choose the Range to menu with  /  buttons, and
press the ENTE switch.
12. Type the high value of the output scale with help  , -
, + switches, and press the OK switch to accept the
value.
PQRM5300 33 Ux Ix xx xx (PS)
, U
, I
, I
, I
,
L2
L3
L1
L2
L3
, Q
, S
, S
, S
L2
L3
L1
L2
, φ
, φ
,
L1
L2
L3
, f
, f
; ρ
, ρ
1
2
3
12
13
,
L3
20201120-V1