Serial port cannot be initialized. Serious hardware failure
256-258 Power EEPROM data is defect or too old
512
Control board EEPROM data is defect or too old
513
Communication time out reading EEPROM data
514
Communication time out reading EEPROM data
515
Application Orientated Control cannot recognize the EE-
PROM data
516
Cannot write to the EEPROM because a write command
is on progress
517
Write command is under time out
518
Failure in the EEPROM
519
Missing or invalid Barcode data in EEPROM
783
Parameter value outside of min/max limits
1024-127
A CAN message that has to be sent, couldn't be sent
9
1281
Digital Signal Processor flash timeout
1282
Power micro software version mismatch
1283
Power EEPROM data version mismatch
1284
Cannot read Digital Signal Processor software version
1299
Option SW in slot A is too old
1300
Option SW in slot B is too old
1301
Option SW in slot C0 is too old
1302
Option SW in slot C1 is too old
1315
Option SW in slot A is not supported (not allowed)
1316
Option SW in slot B is not supported (not allowed)
1317
Option SW in slot C0 is not supported (not allowed)
1318
Option SW in slot C1 is not supported (not allowed)
1379
Option A did not respond when calculating Platform Ver-
sion.
1380
Option B did not respond when calculating Platform Ver-
sion.
1381
Option C0 did not respond when calculating Platform
Version.
1382
Option C1 did not respond when calculating Platform
Version.
1536
An exception in the Application Orientated Control is
registered. Debug information written in LCP
1792
DSP watchdog is active. Debugging of power part data
Motor Orientated Control data not transferred correctly
2049
Power data restarted
2064-207
H081x: option in slot x has restarted
2
2080-208
H082x: option in slot x has issued a power-up wait
8
2096-210
H083x: option in slot x has issued a legal power-up wait
4
2304
Could not read any data from power EEPROM
2305
Missing SW version from power unit
2314
Missing power unit data from power unit
2315
Missing SW version from power unit
2316
Missing io_statepage from power unit
2324
Power card configuration is determined to be incorrect
at power-up
2325
A power card has stopped communicating while main
power is applied
2326
Power card configuration is determined to be incorrect
after the delay for power cards to register
2327
Too many power card locations have been registered as
present
2330
Power size information between the power cards does
not match
2561
No communication from DSP to ATACD
2562
No communication from ATACD to DSP (state running)
2816
Stack overflow Control board module
2817
Scheduler slow tasks
2818
Fast tasks
2819
Parameter thread
2820
LCP Stack overflow
2821
Serial port overflow
2822
USB port overflow
2836
cfListMempool to small
3072-512
Parameter value is outside its limits
2
5123
5124
5125
5126
5376-623
ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on the power
card. The problem could be on the power card, on the gate drive card,
or the ribbon cable between the power card and gate drive card.
WARNING 40, Overload of Digital Output Terminal 27
Check the load connected to terminal 27 or remove short-circuit connec-
tion. Check par. 5-00
WARNING 41, Overload of Digital Output Terminal 29
Check the load connected to terminal 29 or remove short-circuit connec-
tion. Check par. 5-00
WARNING 42, Overload of Digital Output on X30/6 or Overload
of Digital Output on X30/7
For X30/6, check the load connected to X30/6 or remove short-circuit
connection. Check par. 5-32
For X30/7, check the load connected to X30/7 or remove short-circuit
connection. Check par. 5-33
ALARM 46, Power card supply
The supply on the power card is out of range.
There are three power supplies generated by the switch mode power
supply (SMPS) on the power card: 24 V, 5 V, +/-18 V. When powered
with 24 VDC with the MCB 107 option, only the 24 V and 5 V supplies are
monitored. When powered with three-phase AC line voltage, all three
supplied are monitored.
WARNING 47, 24 V supply low
The 24 VDC is measured on the control card. The external 24 VDC backup
power supply may be overloaded, otherwise contact your Danfoss sup-
plier.
WARNING 48, 1.8 V supply low
The 1.8 Volt DC supply used on the control card is outside of allowable
limits. The power supply is measured on the control card.
WARNING 49, Speed limit
The speed is not within the specified range in par. 4-11
Limit [RPM]
ALARM 50, AMA calibration failed
Contact your Danfoss supplier.
ALARM 51, AMA check Unom and Inom
The setting of the motor voltage, motor current, and motor power is pre-
sumably wrong. Check the settings.
ALARM 52, AMA low Inom
The motor current is too low. Check the settings.
®
MG.20.T1.22 - VLT
is a registered Danfoss trademark
Option in slot A: Hardware incompatible with Control
board hardware
Option in slot B: Hardware incompatible with Control
board hardware
Option in slot C0: Hardware incompatible with Control
board hardware
Option in slot C1: Hardware incompatible with Control
board hardware
Out of memory
1
Digital I/O Mode
and par. 5-01
Digital I/O Mode
and par. 5-02
Term X30/6 Digi Out (MCB 101)
Term X30/7 Digi Out (MCB 101)
Motor Speed High Limit [RPM]
and par. 4-13
9 Troubleshooting
Terminal 27 Mode
.
Terminal 29 Mode
.
.
.
9
Motor Speed Low
.
9-7