Danfoss VLT AQUA Drive FC 200 Instruction Manual page 131

Low harmonic drive
Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

6 How to Program the Low Harmonic Drive
22-39 High Speed Power [HP]
Range:
Application
[Application dependant]
dependent*
22-40 Minimum Run Time
Range:
10 s*
[0 - 600 s]
22-41 Minimum Sleep Time
Range:
10 s*
[0 - 600 s]
6
22-42 Wake-up Speed [RPM]
Range:
Application
[Application dependant]
dependent*
22-43 Wake-up Speed [Hz]
Range:
Application
[Application dependant]
dependent*
22-44 Wake-up Ref./FB Difference
Range:
10%*
[0-100%]
6-38
Function:
To be used if par. 0-03
Regional Settings
International selected).
Set power consumption to 85% speed level.
This function is used for storing values needed to tune No-flow Detection.
Function:
Set the desired minimum running time for the motor after a start command (digital input or bus)
before entering sleep mode.
Function:
Set the desired minimum time for staying in sleep mode. This will override any wake-up conditions.
Function:
Motor Speed Unit
To be used if par. 0-02
Configuration Mode
Only to be used if par. 1-00
by an external controller.
Set the reference speed at which sleep mode should be canceled.
Function:
Motor Speed Unit
To be used if par. 0-02
Configuration Mode
Only to be used if par. 1-00
by an external controller controlling the pressure.
Set the reference speed at which sleep mode should be canceled.
Function:
Configuration Mode
Only to be used if par. 1-00,
troller is used for controlling the pressure.
Set the pressure drop allowed as a percentage of the setpoint for the pressure (Pset) before can-
celing sleep mode.
NOTE!
If used in application where the integrated PI controller is set for inverse control
PID, Normal/Inverse Control
in par. 20-71,
tomatically be added.
®
MG.20.T1.22 - VLT
is a registered Danfoss trademark
VLT AQUA Low Harmonic Drive Instruction
has been set for North America (parameter not visible if
has been set for RPM (parameter not visible if Hz selected).
is set for open-loop and speed reference is applied
has been set for Hz (parameter not visible if RPM selected).
is set for open-loop and speed reference is applied
, is set for closed-loop and the integrated PI con-
, the value set in par. 22-44 will au-
Manual