Battery Capacity; Table 21 Battery Calculation - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
 
Auxiliary Power Supply 
Battery Capacity 
Total Standby Current 
(from above) 
 
Total Alarm Current 
(from above) 
 
A.H. for Standby    A.H. for Alarm 
 
 
 
 
 
Notes:   
Use of alternative batteries may result in failure of the panel to meet agency and regulatory requirements and 
may result in shortened battery life. Batteries should be tested regularly and replaced at least every four years. 
If the Battery Trouble indicator activates, the required service should be performed by an authorized agent. 
 
EOL 
Total Currents 
Table 21 Battery Calculation 
Hours of Standby Required per UL864 Standard    AH for Standby 
  A  x 24 Hours 
5 Minutes of Alarm Operation 
per  UL864  Standard,  30  Minutes  of  Alarm 
Operation per ULC‐S527 and 5 Minutes of Alert 
for Two‐stage. 
A  x 0.09 Hours
(For ULC compliance)
A  x 0.6 Hours
Calculated A.H. 
Maximum available battery space: 
Length: 8.07 in., width: 6.61in., height: 7.87 in. 
Maximum battery capacity: 40AH 
 
 
× 0.00082 
Standby 
Standby 
(For UL compliance)
 
 
De‐rating 
Factor 
X 1.25 
 
63 
 
0.00082
 
Alarm 
 
Alarm 
 
AH for Alarm 
 
A.H. Required Battery 
Capacity 
 
 
 
 
 