Installation and Operation Manual
Wiring Separation
All high voltage and non‐power limited wiring must be separated from power limited wiring. A separation of at
least 1/4 inch must be maintained with high voltage and non‐power limited wiring running in separate conduit
openings from power limited wiring.
Figure 17 Wiring Terminals Location
Power Supply Wiring
AC Connection
Wire the AC supply to the power supply on the back of the enclosure. The supply should originate from a
dedicated 15A branch circuit. It should be provided with a breaker or other means of isolation that must be
colored red.
24