Wiring Separation 
All high voltage and non‐power limited wiring must be separated from power limited wiring. A separation of at 
least 1/4 inch must be maintained with high voltage and non‐power limited wiring running in separate conduit 
openings from power limited wiring.   
 
Figure 17 Wiring Terminals Location 
 
Power Supply Wiring 
AC Connection 
Wire the AC supply to the power supply on the back of the enclosure. The supply should originate from a 
dedicated 15A branch circuit. It should be provided with a breaker or other means of isolation that must be 
colored red.   
24 
 
 