Installation and Operation Manual
INSTALLATION
Cautions
1. Remove the PCB for any procedure that may cause dust, metal shavings, grease, or such matter to affect the
operation of the boards or get in contact with the units.
2. Disconnect all sources of power prior to installing or removing modules, connecting or disconnecting wiring
and programming jumpers.
3. Group the incoming wires through the top of the enclosure. For easy identification and neatness use a wire
tie.
4. DO NOT insert cables through bottom of the box. This space is reserved for Batteries.
Control Panel Location
The control panel should be located near an exit at ground level where the normal ambient temperature is
maintained within the control panel specification (see the Specifications and Features section). The unit should
be in an area free of dust, vibration, moisture, and condensation. Any auxiliary battery box or other accessory
not connected through a protective device or a circuit designed for remote connection must be within 20 ft. and
in the same room, connected through the electrical conduit.
Control Panel Installation Notice
The cabinet must be fastened securely to a clean, dry, shock‐free, and vibration‐free surface in a protected
environment. Consider the following when mounting the cabinet:
Mounting height for visual and manual access to the Display Board
Weight and size of cabinet
Local mounting codes
When mounting the cabinet, position the cabinet clear of obstructions so that the door can open freely and
indicators and controls are easily accessible.
The fire alarm control panel must be mounted in a properly accessible location, as required by the applicable
codes and the AHJ.
Installation must be done by qualified personnel who have thoroughly read and who understands these
instructions.