Nou - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
NOU 
 One NOU can support two independent notification appliance circuits. 
 Circuit topology support: Class A or Class B.   
 Maximum Current: 2A per NAC circuit, 4A total per NOU 
 NOU address is set by the rotary switch on the board. The valid address range is 1~5.   
 
 
 
 
The NOU must be set to a correct address before use. Please refer to Unit Address 
Setting section for detail. 
 
 
Figure 9 NOU 
13 
 
 