Appendix-B: Wire Selection Guide; Slc Wire Selection Guide; Table 16 Addressable Loop Wiring - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
Appendix‐B: Wire Selection Guide 
SLC Wire Selection Guide 
Maximum Loop Current = 100mA@NSB, 220mA@Alarm 
Maximum Loop Capacitance = 0.1uF 
Wire Gauge 
Wire 
(AWG) 
Resistance 
(ohms/km)
12 
5.31 
13 
6.69 
14 
8.45 
15 
10.6 
16 
13.5 
17 
16.3 
18 
21.4 
 
 
 
Table 16 Addressable Loop Wiring 
Maximum Wiring Run to Last Device 
Maximum current 
90mA 
ft 
15099   
4603   
11985   
3654   
9488   
2893   
7564   
2306   
5939   
1811   
4919   
1500   
3747   
1142   
 
 
Maximum current 
150mA 
ft 
9060   
7191   
5693   
4538   
3563   
2951   
2248   
58 
Maximum current 
220mA 
ft 
2762   
6177   
2192   
4903   
1736   
3882   
1384   
3094   
1086   
2430   
900   
2012   
685   
1533   
 
1883   
1495   
1183   
943   
741   
613   
467   