Installation and Operation Manual                                                                                                 
Troubleshooting 
The following are common methods to solving Circuit Troubles, Ground Fault, Battery and Common troubles. 
Circuit Trouble 
Normally when a circuit trouble occurs, the Trouble LED will be illuminated and the common trouble relay will 
be active. Usually a relative event can be shown on the LCD event list view. Use these indications to correct the 
fault, check for open wiring on that particular circuit loop. 
 
In Addressable Loop Circuit 
In Notification Appliance Circuit 
In Auxiliary Power Circuit 
 
Ground Fault
 
This panel has ground fault detection. To correct the fault, check for any external wiring touching the chassis or 
other Earth Ground connection. 
The maximum resistance for testing ground fault detection for extended wirings other than the network is 6.6 
kohm. 
The maximum resistance for testing ground fault detection for network wiring is 60 ohm. 
 
Battery Trouble 
Check for the presence of batteries and their conditions. Low voltage (below 20.4V) will cause a battery trouble. 
If battery trouble condition persists, replace batteries as soon as possible. 
Common Trouble 
If only a common trouble is indicated on the main panel and none of those above confirming trouble indicators 
are on, then check the following for possible fault 
Any missing interconnection wiring 
Improperly secured cabling 
 
 
Table 6 Circuit Trouble 
The minimum resistance to   
test open fault (Ohms) 
500K 
500K 
NA 
 
 
37 
The maximum resistance to 
test short fault(Ohms) 
10 
10 
 