Installation and Operation Manual
LCD Display
The LCD can display 8 events at a time. Users can browse more events by pressing the up/down button until the
first event or last event message is reached.
Events are displayed according to the following rules:
1: Events priority:
Alarm > Supervisory > Trouble > Other Signal>Output
2: Within events of the same priority, all events are displayed in order of occurrence, the latest being displayed
first.
However, the sequence of alarm event is configurable.
Lamp Test
When selected, the lamp test activates the LCD, the buzzer, and turns on all the LEDs on the user interface. It
then reverts to its previous state.
To initiate a lamp test, proceed as follows:
1: Press the "MENU" button.
2: Select "Lamp Test "to run.
The lamp test operates the indicators only on the units being operated. No record is reported to the system
history.
50