Installation and Operation Manual
System Checkout
The following are the recommended steps that should be followed before and during the powering up of the
FW106/FW106C.
Before Turning the Power ON
1. To prevent sparking, DO NOT connect the battery first. Connecting the batteries should only be done once the
system has been powered from the main AC Supply.
2. Check all field (external) wiring for opens, shorts, and ground.
3. Check that all interconnection cables are secure and that all connectors are plugged in properly.
4. Check all switches for proper setting.
5. Check the AC power wiring for proper connection. Observe/check slide switch position.
6. Close the front cover plate before powering the system from main AC supply.
Power‐up Procedure
1. After completing Before Turning the Power ON procedures, power‐up the panel.
The green AC ON LED should illuminate.
2. Since the batteries are not connected, the Battery Trouble LED should illuminate, the
Trouble LED should flash and the Trouble Relay (on the main board) will be active.
3. Connect the batteries while observing correct polarity; the red wire is positive (+) and black wire is negative
(‐).
4. All indicators should extinguish except for normal power AC ON green LED.
36