Network Circuit 
 
Addressable Loop 
Circuits 
 
 
System Components 
Components Overview 
Table 3 describes the FW106/FW106Ccomponents. 
Model 
FW201/FW201C 
FW391 
FW397 
FW327 
FW337 
FW347 
FW357 
 
 
 
Class B circuit 
For up to 110 panels and/or remote annunciators connection 
Communications protocol: CAN 
Max. line capacitance = 0.05 uF 
Max. line resistance = 25 Ohm 
Maximum Current (short ): 0.4A 
Class A/Class B circuit 
252 addresses: detectors and modules max 
Output voltage range: 20.2V ~ 26.2V 
Maximum normal standby current: 100mA 
Maximum alarm current: 220mA 
Max. line capacitance = 0.1 uF 
Max. line resistance = 10 Ohm 
Table 3 System Components 
Description 
AMI(Advanced Machine Interface) 
PTU(Power‐supply Transformer Unit) 
PCU (Power‐supply and Charger Unit) 
ALU (Addressable Loop Unit) 
NOU (Notification Output Unit) 
ROU (Relay Output Unit) 
XNU(External Network Unit) 
 
 