Positive Alarm Sequence (Pas); Figure 33 Positive Alarm Sequence - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
Positive Alarm Sequence (PAS) 
When an alarm causing device associated with a zone with PAS feature is initiated, the alert condition is reported 
on the panel. The activation of all system evacuation signals are delayed for 15 seconds (PAS delay time) waiting 
for a manual acknowledgement response.   
If  no  response  is  received  within  15  seconds,  the  panel  proceeds  to  activate  system  evacuation  signals.  See 
Figure A. 
If  the  alarm  event  is  acknowledged  during  the  PAS  delay  time,  the  programmable  PAS  investigation  time  (180 
seconds) is added to the PAS delay time before system evacuation signals are activated. See Figure B. 
However,  if  a  2nd  alarm  is  initiated  anytime  during  the  PAS  delay  time  or  PAS  investigation  time,  the  system 
evacuation signals are immediately activated. See Figure C. 
Pressing the Reset button at anytime during the PAS sequence will initiate a reset condition and try to restore 
the panel to stand‐by state. 
 
 
Figure 33 Positive Alarm Sequence 
 
 