System Wiring; Wiring Notes; Power Limiting; Wiring Entering The Enclosure - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
SYSTEM WIRING 
Before connecting the field wiring, check the wiring for opens, shorts, grounds, and stray voltages. 
Damage may result if a high‐voltage insulation tester is used on wiring while connected to the control panel 
and field devices. 
 
Terminate the field wiring to the main board in accordance with the diagrams in the SYSTEM WIRING section 
and in the system design documents. 
All wiring must be in accordance with local codes, National Electrical Code, and Canadian Electrical Code. 
 
Wiring Notes 
Basic system wiring and detector locations must be in accordance with NFPA 72 and CAN/ULC‐S524 or other 
applicable codes and instructions from the appropriate local authority having jurisdiction. 
Devices that may be satisfactorily used with the control panel are shown in the Appendix‐A: Compatible Devices. 
Wire reference data are listed in Appendix‐B: Wire Selection Guide. 
Power Limiting 
In accordance with NEC Article 760 and UL 864, all power limited fire protective signaling conductors must be 
located at least 1/4 inch away from all of the following wiring located within a control panel: 
Electric light 
Power 
Class 1 or non‐power limited fire protective signaling conductors 
To meet these requirements, the following guidelines must be observed when installing modules and wiring to 
this control panel. 
When installing power limited field wiring, the installer must comply with NEC article 760, which states: 
The fire alarm power‐limited circuits are installed using Types FPL, FPLR, FPLP or permitted substitute cable, 
provided these power‐limited cable conductors extending beyond the jacket are separated by a minimum of 
0.25 in. (6.35 mm) or by a nonconductive sleeve or nonconductive barrier from all other conductors. 
If  energy  limited  cable  or  equivalent  is  not  used  within  the  FW106/FW106C  enclosure,  then  the  following 
guidelines do not apply. In that case, be sure to follow standard wiring practices. 
Wiring Entering the Enclosure 
Non‐Power Limited Wiring ‐ Wiring entering the enclosure from the bottom left side and right side of the 
enclosure is considered non‐power limited wiring. Wiring must be in the shortest route and must not overlap 
any other wiring.   
 
 
 
Power Limited Wiring ‐ Wiring entering the enclosure from the upper left side of the enclosure or the right 
side is considered power limited. Wiring must be in the shortest route and must not overlap any other wiring. 
 
WARNING 
23 
 
 

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fw106c

Table of Contents