Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
XNU 
 TheFW106/FW106C control panel communicates to panels/annunciators, up to 110 nodes on a network. 
 Circuit topology support: Class B.   
 XNU  address  is  set  by  configuration  from  the  panel  or  configurator.  The  valid  address  range  of  the 
FW106/FW106C or a compatible annunciator is 1 to 110. 
 
Battery 
FW106/FW106C can support 40 AH sealed lead‐acid batteries within code requirements for up to 24 hours 
normal standby plus 30 minutes alarm. 
Batteries must be replaced when they fail to provide the control panel with the required standby and alarm 
power or after 4 years, whichever happens first. 
Please refer to Battery Calculations to select an appropriate Battery Capacity. 
 
The XNU must be set to a correct address before use. Please refer to Unit Address 
Setting section for detail. 
 