Appendix-C: Quantities Of Notification Appliances; Table 19 Maximum Numbers Of - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
Appendix‐C: Quantities of Notification Appliances 
 
Table 19 lists the maximum number of notification appliances (FW961R / FW961W, FW971R / FW971W, 
FW981R / FW981W, FW962R / FW962W, and FW982R / FW982W) per NAC in the worst case scenario for 
Synchronization system. 
Model No. 
FW961R/FW961W 
FW971R/FW971W 
FW981R/FW981W 
FW962R / FW962W 
FW982R / FW982W 
 
 
 
 
 
Table 19 Maximum Numbers of NA 
Description 
Horn/Strobe Light 
Horn 
Strobe Light 
Multi‐candela Horn Strobe 
Multi‐candela Strobe 
If these 3 types of notification appliances are mixed in the same circuit, the total 
current of the circuit must be <= 2 Amperes. 
 
 
Maximum number per NAC 
60 
15 
110 
16 
33 
33 
 