Configuration And Maintenance; Pc Configuration; Control Panel Access Control - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
Configuration and Maintenance 
PC Configuration 
Programming the panel may be done by temporarily connecting the programming port to a computer. This is 
the recommended method to configure the panel. 
The Maple Armor FW401 Configurator software is available to configure of the control panel using a Personal 
Computer (PC) with an Ethernet port. This allows ease of operation by preparing the program in advance and 
downloading it to the control panel by a simple and fast operation. 
Control Panel Access Control 
The FW106/FW106C provides configuration and maintenance functions to set and control various features in 
the system.   
The configuration and maintenance functions are protected by access control. The following levels of security 
protect the system from unauthorized use: 
Level 1 – Locked Door 
Level 2 – Locked Door and 4‐digit Password, Level 2 provides control functions. 
Level 3 – Locked Door and 4‐digit Password, Level 3 provides control functions and parameter change 
functions. 
To access the maintenance features, press the "MENU" button and select "Access To System", enter the four 
digit code when prompted, then press "OK".   
 
 
 
 
The User Level is also accessible from the Remote LCD Annunciators. 
 
 
51 
 