Installation and Operation Manual
Field Device
When the trouble condition has been noted, pressing ACKNOWLEDGE button will silence the buzzer and change
the trouble LED to steady ON.
The panel has a 24‐hour Supv/Trouble Resound function. If the trouble condition is not corrected and the
Supv/Trouble Resound Reminder timer has elapsed, the panel will re‐annunciate the trouble condition.
When the indicated trouble condition has been cleared, the system reverts to normal standby condition
automatically.
Supervisory Conditions
In case of a supervisory condition, the system supervisory LED activates (ON – flashing) and the buzzer activates
in supervisory pattern. The LCD notes the supervisory event and the buzzer sounds in supervisory pattern.
Supervisory event can be configured as latched or non‐latched by setting from the system attribute interface.
Returning to normal condition will not cause the supervisory event to disappear until manually reset if it is
Bus_Open
Bus_CrossPower
NOU_CircuitTrbl
Heat_SensingError
Smoke_Contamination
Smoke_SensingError
Init.Device_Duplicate
Init.Device_Illegal
Init.Device_Missing
Init.Device_WrongType
Init.Device_Vol.Abnormal
Init.Device_GeneralTrbl
The addressable loop circuit is open
The addressable loop circuit wire is cross
power
The notification appliance circuit is
malfunctioning (open, short, grounding, etc.)
The heat detector sensing has an error
The chamber of the smoke detector is
contaminated
The chamber of the smoke detector is
severely dirty and can't be used
Two or more devices have the same address
The device is working online, but it is not
configured
The device is configured, but it is missing
The device type is incorrectly configured
The device detects abnormal line voltage
The device has internal hardware trouble