Installation and Operation Manual
Event History
The control panel includes a non‐volatile memory recording 5000events, plus a separate 1000 alarm‐only events.
Identified alarm, trouble, supervisory, status, and other significant events will be recorded along with the date
and time of occurrence. These can be viewed by operating the front panel push buttons.
To recall past events, proceed as follows:
Press the "MENU" button.
On the "MENU" display, select "Archive".
Press the "Enter" button.
Use the up button next to the LCD to see the previous event display.
Use the down button next to the LCD to see the next event display.
The history record rule is:
New events overwrite old events when filled.
The events are sorted by time occurrence sequence.
Events recorded in the history are:
Alarm, Trouble, Supervisory, and Monitor conditions
Alarm silence/Resound
System reset
System startup
Enable/disable function
Start and stop of Walk Test
Trouble/supervisory reminder
Trouble/supervisory restored to normal