Event History - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
Event History 
The control panel includes a non‐volatile memory recording 5000events, plus a separate 1000 alarm‐only events. 
Identified alarm, trouble, supervisory, status, and other significant events will be recorded along with the date 
and time of occurrence. These can be viewed by operating the front panel push buttons. 
To recall past events, proceed as follows: 
Press the "MENU" button. 
On the "MENU" display, select "Archive". 
Press the "Enter" button. 
Use the up button next to the LCD to see the previous event display. 
Use the down button next to the LCD to see the next event display. 
The history record rule is: 
New events overwrite old events when filled. 
The events are sorted by time occurrence sequence. 
 
Events recorded in the history are: 
Alarm, Trouble, Supervisory, and Monitor conditions 
Alarm silence/Resound 
System reset 
System startup 
Enable/disable function 
Start and stop of Walk Test 
Trouble/supervisory reminder 
Trouble/supervisory restored to normal 
 
 
 
 
46 
 