Two-Stage; By-Pass; Auto Addressing; Figure 34 Two-Stage Alarm - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
 
Two‐Stage 
When an alarm causing device associated with a zone with two‐stage feature is initiated, it will enter first stage 
alarm and the alert condition is reported on the panel. A countdown timer will start at the moment and buzzer 
will sound in alert tone. Notification appliance will sound in alert tone. 
If the timer counts down to 0 or pressing "To Second Stage" button, system will enter second stage alarm status. 
Alarm  event  will  display  on  LCD,  along  with  buzzer  with  alarm  tone  and  notification  appliance  in  alarm  tone 
(Temporal 3). 
If "Auto Alarm Signal Cancel" button or "Signal Silence" button is pressed during first stage alarm, the system will 
enter  the  automatic  alarm  signal  cancel  status.  Automatic  alarm  signal  cancel  event  will  display  on  LCD.  The 
countdown timer is cancelled, buzzer keeping in alert tone, and notification appliance sounding in alert tone (if 
it's not silenced).   
 
 
Figure 34 Two‐Stage Alarm 
By‐pass 
The by‐pass function is provided for user if they don't want to receive message from specified devices. 
 
Auto addressing 
Auto addressing mode which is applied to assign addresses for field devices by panel. When panel goes 
into Auto Addressing mode, devices installed on this loop will be automatically assigned addresses in 
sequence  which  is  convenient  for  filed  commissioning.  Please  refer  to  the  programming  manual  for 
details.  
 