Installation and Operation Manual
Two‐Stage
When an alarm causing device associated with a zone with two‐stage feature is initiated, it will enter first stage
alarm and the alert condition is reported on the panel. A countdown timer will start at the moment and buzzer
will sound in alert tone. Notification appliance will sound in alert tone.
If the timer counts down to 0 or pressing "To Second Stage" button, system will enter second stage alarm status.
Alarm event will display on LCD, along with buzzer with alarm tone and notification appliance in alarm tone
(Temporal 3).
If "Auto Alarm Signal Cancel" button or "Signal Silence" button is pressed during first stage alarm, the system will
enter the automatic alarm signal cancel status. Automatic alarm signal cancel event will display on LCD. The
countdown timer is cancelled, buzzer keeping in alert tone, and notification appliance sounding in alert tone (if
it's not silenced).
Figure 34 Two‐Stage Alarm
By‐pass
The by‐pass function is provided for user if they don't want to receive message from specified devices.
Auto addressing
Auto addressing mode which is applied to assign addresses for field devices by panel. When panel goes
into Auto Addressing mode, devices installed on this loop will be automatically assigned addresses in
sequence which is convenient for filed commissioning. Please refer to the programming manual for
details.
45