Manual Station Response; Drift Compensation; Alarm Verification; Figure 32 Alarm Verification - Maple Armor FW106 Installation And Operation Manual

Fire alarm control panel
Table of Contents

Advertisement

Installation and Operation Manual                                                                                                 
General Trouble 
Sensing Error 
Contamination 
Please refer to the Trouble Conditions section for more detail on each event type. 
Manual Station Response 
Addressable manual stations may be intermixed on the circuit with proper response programmed into the 
control panel. 
Drift Compensation 
The Drift Compensation is built into a compatible detector and is not performed by the panel. Drift 
compensation automatically adjusts for gradually increasing effects of dust and other accumulations of dirt in 
the detectors. It will adjust the thresholds to compensate for a detector going dirty according to the gradual 
change in the normal clean air value received. When it can no longer compensate for an increasingly dirty 
detector, a dirty detector trouble (Contamination trouble) is indicated for that device. 
Alarm Verification 
The Alarm Verification function is supported by this panel. One typical alarm verification phase can be divided 
into 2 periods. The first period is a retard period in which no alarm reports on the Fire Alarm Control Panel 
(FACP). The second period is a confirmation period in which alarm reports on the Fire Alarm Control Panel if a 
device is in alarm status. The detail alarm verification phase is illustrated in Figure 32.   
 
A ‐ Smoke detector goes into alarm. (LED on device turns to steady on) 
AB ‐ Retard Period: Fire Alarm Control Panel senses detector in alarm and delays alarm signal for 50s. During 
this period, no alarm event reports on the Fire Alarm Control Panel. 
BC ‐ Confirmation Period: Detector is operational for alarm at point B. If the detector is still in alarm at point B, 
the Fire Alarm Control Panel will report an alarm. If the detector is not in alarm, the system returns to standby. 
If the detector re‐alarms at any time during the confirmation period the Fire Alarm Control Panel will alarm. 
The period length is 60s. 
CD – Restart next alarm verification period if new alarm occurs. 
 
Figure 32 Alarm Verification 
 
43 
 
 
 

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fw106c

Table of Contents