Installation and Operation Manual
Specifications and Features
The specifications and features of the FW106/FW106C Control Panel are described in Table 2.
General
Environmental
Primary Supply
Secondary Power
Supply
Power Outputs
Relays Output
Notification Appliance
Circuits
Table 2 FW106/FW106C Control Panel Specifications
Digital signal processor based design, fully configurable from front panel with
password protection
Operating temperature : 32 ‐ 120F (0 ‐ 49C)
Relative humidity : Up to 93% @ 90F (32C)
To be installed in normal dry indoor environment only
110 ‐ 120 VAC 60Hz (3.86A), or
220 ‐ 240 VAC 50Hz (1.96A)
Two 12V in series lead‐acid batteries set
Charging capacity: 40AH
Internal power supply for
AMI
ALUs and Addressable Loop Circuits
NOUs and Notification Appliance Circuits
XNUs, External Network Circuits
ROUs
One auxiliary power supply
Non‐Resettable/Resettable Power Output (configurable)
Power limited
24VDC
Output current: 500mA in normal standby, 1200mA in alarm
Power Factor Rating: 0.35
Special application: Compatible devices are the Annunciator Model FW121 /
FW121C /FW122W / FW122R / FW122CW / FW122CR / FW123 / FW123C and IO
Module Model FW821.
One programmable relay
4 non‐programmable status relays
Status: Alarm, Supervisory, Trouble, Monitor
Form C Contact
Contact Rating: 2A 30VDC
Power Factor Ration:0.35
Total of 10 circuits supported, total power available 8A
2 Class A or 2 Class B circuits on each NOU
Maximum Current: 2A per NAC circuit
Alarm Voltage: 24V nominal
Bell code: Temporal 3
Panel supports one regulated 24 VDC NAC, or up to 10 special application 24VDC
NAC. Refer to Table 20 for specific appliances/devices.
Max line loss: 1.8 V.
7