External Network Circuit Wiring 
External network circuit can address up to 110 panels and/or remote annunciators.   
FW106/FW106C control panel can connect to panels/annunciators by using External Network Unit. 
 
Remote Device Power – The control panel auxiliary power can provide power for 4 annunciators. Each address 
on the circuit must be fully powered from either auxiliary power of control panel UL/ULC Listed power supply 
for use in fire alarm systems. 
When connecting panels/annunciators on the external network circuit, the data wires must be daisy chained 
and with no T‐taps to preserve the integrity of the data. The following diagrams show the proper wiring. 
External Network Circuit Wiring ‐ Class B 
 
About the XNU Jumper 
Each XNU has an internal jumper on its upper right side which must first be correctly configured. 
 
 
 
Figure 27 External Network Circuit Wiring ‐ Class B 
 
 
If  this  XNU  is  located  at  the  end  of  the  external  network  circuit,  the  jumper 
must be switched to "ON". 
 
 
 
 
 
 
 
 
 