UL/cUL RESIDENTIAL FIRE & BURGLARY INSTALLATIONS
This product has been tested and found in compliance with the following standards: UL1023 Household Burglar-Alarm
System Units, UL985 Household Fire Warning System Units, ULC-S545 Residential Fire Warning Systems Control Units
and ULC-S304 Security Level I Control Units, Accessories and Receiving Equipment for Intrusion Alarm Systems. For ULC
Installations refer to the Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540:
- Use only the compatible power supply referenced in this Installation Manual. 24 h standby power must be provided for
fire applications and 4h for burglary only applications (AC trouble must be transmitted to SRC within 60 minutes).
- Priority of signals on the Panel is set as Fire, CO, Burg, Panic, Aux and then Flood.
- Use at least one compatible listed Smoke Detector for Fire Installations.
- The entry delay shall not exceed 45 sec (UL) and 180 sec (ULC Security Level 1).
- The exit delay shall not exceed 120 seconds (UL).
- The control panel supports the Temporal 3 pattern for fire alarm notification
- Test transmission cycle shall be set for 7 days transmission for Residential Fire applications, or 30 days for Residential
Burglary only applications.
- If Wireless Repeater is required to be employed with a RF Smoke Detectors or CO Detectors, two repeaters must be
installed to cover EACH Smoke Detector and/or EACH CO detector.