Calculating General Settings For Analogue Inputs 8I 2U - ABB Relion 650 Series Applications Manual

Transformer protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 3
RET650 setting examples
3.1.1

Calculating general settings for analogue inputs 8I 2U

The analogue input has the capability of 8 current inputs (1 A) and 2 voltage inputs.
The 145 kV current CTs (three phase current transformer group) are connected to inputs 1 – 3
(L1, L2, L3).
The 22 kV current CTs (three phase current transformer group) are connected to inputs 4 – 6
(L1, L2, L3).
The 145 kV neutral point CT is connected to input 7 (IN).
The input 8 is not used. The input is used for connection of low voltage side CT (not in this
application)
The 22 kV phase-to-phase (L1 – L2) VT is connected to input 9.
The 22 kV open delta connected VT (residual voltage) is connected to input 10.
1.
Set the 145 kV current transformer input 1.
1.1.
1.2.
1.3.
2.
Set current inputs 2 and 3 to the same values as for current input 1.
3.
Set the 22 kV current transformer input 4.
3.1.
3.2.
3.3.
4.
Set current inputs 5 and 6 to the same values as for current input 4.
5.
Set the 145 kV neutral point current transformer input 7.
5.1.
5.2.
34
Only settings that need adjustment due to the specific application are
described in setting examples. It is recommended to keep the default values
for all settings that are not described. Refer to Technical manual for setting
tables for each protection and control function.
Refer to setting guideline section in Application manual for guidelines on how
to set functions that are not presented in setting examples.
Use parameter setting tool in PCM600 to set the IED according to calculations
for the particular application.
Set
CTStarPoint1 to ToObject
(The CT secondary is earthed towards the protected transformer)
CTSec1 to 1 A
Set
(The rated secondary current of the CT)
CTPrim1 to 300 A
Set
(The rated primary current of the CT)
Set
CTStarPoint4 to ToObject
(The CT secondary is earthed towards the protected transformer)
CTSec4 to 1 A
Set
(The rated secondary current of the CT)
CTPrim4 to 2000 A
Set
(The rated primary current of the CT)
Set
CTStarPoint7 to ToObject
(The CT secondary is earthed towards the protected line)
CTSec7 to 1 A
Set
© Copyright 2011 ABB Power Grids. All rights reserved
1MRK 504 124-UEN B
GUID-C2285D25-032F-4709-B31C-D52A2150E78A v2
Transformer protection RET650
Application manual