14.5 General Settings

The General Settings Tab enables you to configure the HW according to the Electronic Device
(IED) integrated in the CB and to the application characteristics, such as the current ratings,
network frequency and single-line diagram. It manages enabling of a number of automation functions.
Fig. 28
14.5.1 Main Settings
The Main settings dialogue window allows the user to configure the nominal values of the analog
input channels and to set default values for each sensor type.
The Main Settings for the Analog inputs are:
– Set the Nominal Primary Current, i.e. the rated Nominal current of the application
– Check the CCT Presence tick box
– Set the CCT earth Nominal Primary Current value
– Set the Rated Network Frequency value, by default 50 Hz.
Fig. 29
Do not make any changes to the eVM1 configuration unless you are familiar with the eVM1
Warning!
and its Operating Tool. Changing the nominal currents and frequency values of the Main
Settings might result in malfunction of protection functions.