Finishing installation on page 23 tells how to finish installation and test rack functions Contacting ETC For questions about Sensor Delta system delivery or general information, contact ETC Customer Service. When contacting ETC, always tell the representative you have a Delta system: United States customer service Tel: (800) 688-4116.
5. Obtaining ETC approval to energize the system You need ETC approval to apply power to your dimming system. You can get pre-approval for some installations during the purchase process, or pass a wiring inspection by an authorized ETC representative after the system is installed.
For good control access, install racks so the Control Electronics Module (CEM) is between three and five feet (1–1.5 metres) from the floor. In SR12D and Figure 2: Sensor rack SR24D racks, the CEM is in the bottom slot. In the SR48D rack, the CEM slot clearances is in the middle.
Split bus Sensor Delta systems include integrated 175 amp disconnect switches for main power. A disconnect switch controls input and output phase power for 12 dimmer slots. SR12D racks have one disconnect switch, SR24D racks have two and SR48D racks contain four. Before performing maintenance in the left-side Dimmer bay, turn all disconnect switches to Off .
If you cannot fix a problem, or the module breaker continues to trip 1. If the breaker continues to trip or if you find a wiring problem you cannot correct, contact ETC Technical Services or your authorized ETC representative. See Contacting ETC Technical Service on page 29.
D20AF the top of the rack: The first above the CEM backplane D20AF three protect slots 1-12, the second three slots 13-24, etc The second fuse in the first 1 2 3 4 5 set also provides operating D20AF power to the cooling fan...
Changing Installation Rack modules All Sensor Delta rack modules slide in and out of their slots and are ready to start dimming immediately. Although Sensor modules, including the CEM, can be replaced with power on, always turn rack power off at the disconnect switch in the Auxiliary bay or at the main circuit breaker.
1. Use the mounting slot dimensions to mark the hole locations. You must supply your own 3/8 inch (10mm) mounting hardware. Note: The Control Electronic Module (CEM) on SR12D and SR24D racks is located near the bottom of the rack. Install these racks at least 36 inches (1 meter) above the floor for easy access to rack controls.
Securing floor-standing SR48D racks Floor-standing SR48D racks must be bolted to a wall for stability. For greater stability, you can also add floor-mounted securing hardware. Note: Installing securing hardware in the SR48D floor mounting holes does not eliminate the requirement for bolting the rack to the wall. 1.
Vibration damping fittings are available as an option for wall mounted racks Align the center of the fitting over the (SR12D and SR24D). The wall must be strong enough to hold the racks. See diagram hole location and mark the...
Connecting power wiring All connections for power wiring are made inside the attached auxiliary bay. ETC recommends routing line (or feeder) cables first and load wires last. Note: Line and load wires used with Sensor Delta dimming systems must be copper.
Connecting the line feed wires Line feed cables are terminated in the racks connections bay on 175 amp switch assemblies or on standard bus bars. 1. Pull the line phase and ground cables to the rack through the openings you prepared previously.
Attaching wires from the loads Wires from loads are connected to breaker terminals in the auxiliary bay on the right side of the rack. Breaker terminals are organized in pairs, connected by a shared ground wire terminal. Each terminal is identified by a dimmer number label.
DMX512 and ETCLink data connections This section contains instructions for connecting Sensor racks to existing DMX512 or ETCLink data cables. For information about installing DMX512 or ETCLink data cables in your facility, refer to Appendix C: Installing a simple DMX512 or ETCLink network on page 35. Note: Data cables can enter the rack from either the module or connections bay.
Page 19
1. Make a conduit opening in either top, bottom or side of the rack where the data cable will enter. Note: SR12D and SR24D racks have top and bottom conduit knockouts, SR48D racks have top and bottom access panels. All have a left-side conduit knockout level with the internal data connection terminals.
Page 20
Note: SR12D and SR24D racks have top and bottom conduit knockouts, SR48D racks have top and bottom access panels. All have a left-side conduit knockout level with the internal data connection terminals.
Page 21
DMX512 and ETCLink network terminations in multiple racks When you connect data cables to multiple racks (series connections), you must connect an input and output cable to each data port and turn off termination for all racks except the last in the series. 1.
SR12D and SR24D to compensate for the heavier SR48D door. SR12D and SR24D – Insert the bottom hinge into the slot on the bottom of the rack and attach it to the frame with two 10-32 x 1/2"...
Page 24
Taper pin [ ] or [ ] SR48D lower hinge SR12D and SR24D lower hinge Figure 32: Installing the bottom taper pin 4. Hold the door in place and insert the other taper pin, narrow end down, through the top hinge and washer.
Page 25
Warning! – Power must be turned OFF when you perform this procedure. 1. Clean out dust, metal scraps or other debris from the rack interior. Note: ETC recommends vacuuming the rack interior before installing modules. 2. Check for loose connections, bare wires or damaged insulation.
Page 26
Checking control network wiring with the CEM removed You should check your control network wiring at the wallplate XLR connector station farthest from your dimmer rack(s). Warning! – Power must be turned OFF when you perform this procedure. 1. Remove all Control Electronics Modules (CEMs) from your dimmer racks. Checking the DMX512 network 1.
Page 27
Optional – Checking line voltages on the phase bus bars You can check the voltages on your phase bus bars with a Digital Voltmeter (DVM) before installing your modules. Warning! – Line voltages are present on the phase bus bars during this procedure.
Installing rack modules Sensor Delta dimming and control modules are easily slid into place by hand. Installing dimmer modules 1. Inspect each dimmer module for loosened components or other shipping damage. 2. Slide dimmer modules into the rack. If you are installing a mix of module types, consult the included job drawings for the correct module order.
Are all distribution cables landed and properly terminated? (Any circuits not landed must be clear or capped off.) Do all control cables meet spec? (See ETC installation drawings or Table 6 : Network cable requirements on page 36.) Are DMX512 and ETCLink data cables routed as specified in the...
Testing an installed CEM rack After finishing installation, use this procedure to perform a functional check. Note: Go over the Sensor Delta installation checklist on the previous page before energizing the rack. 1. Make sure power is disconnected at the main circuit breaker or at the disconnect switches in the Auxiliary Bay.
Page 31
8. Replace the CEM, reset the module safety stops and close the rack door. 9. Turn all the Auxiliary Bay dimmer circuit breakers to On. 10. If possible, apply power and test your system with the facility control system 11. Deliver all ETC documentation to the system operator. Sensor Delta Dimming Installation Guide...
Appendix A: Sensor Delta specifications Dimensions SR12D – 25.8 in. high x 33.5 in. wide x 13.3 in. deep – 65.5cm high x 85.1cm wide x 33.8cm deep SR24D – 45.8 in. high x 33.5 in.wide x 17.2 in. deep –...
Delta Rack Auxiliary Bay. Advanced Features designations Sensor Delta Dimming systems equipped with ETC’s Advanced Features (AF) dimmer circuit reporting capability require AF compatible installation racks and dimmer modules. Advanced Features is available for both 120 and 230 volt Delta systems.
Page 34
Input Power: Input Power: 3 phase, 3-wire, 50/60Hz, 3 phase, 3-wire, 50/60Hz, Dimmer Rack Model Delta Delta For use with ETC DELTA For use with ETC DELTA Sensor Delta rack SR48D 120VAC dimmer modules only dimmer modules only product label...
Adding to an existing network, or installing a complex network requires technical assistance from an authorized ETC representative and is not covered by these instructions. Note: Use this appendix for guidance only. Your data networks must be designed and installed by qualified personnel and comply with your state and local electrical codes.
Page 36
Installing conduit and cables After planning your network, pull your data cables and accessory wires. Note: ETC recommends installing network cables in grounded metal conduit. 1. Install data conduit and backboxes according to local electrical codes. Note: Do not run DMX512 or ETCLink networks in the same conduit as load or line power wiring.
Page 37
Other connections to the networks are made through wallplate connectors installed on the network cable. Wallplate connectors from ETC install in standard industry backboxes. A single wallplate connector uses a one-gang backbox. Each additional connection increases backbox size by one gang.
Page 38
Connecting terminals to the network cable ETCLink connector DMX512 connector ETCLink DATA INPUT PUSH DMX512 numbers are on top Male RJ5 socket ETCLink plug numbers are on bottom Female RJ5 socket Figure 44: DMX512 and ETCLink wallplate terminals Both DMX512 and ETCLink terminals connect to the network with eight pin terminal plugs.
Page 39
There should be one cable end and one wire in each slot on the plug-in terminal. The ETCLink network needs to have an ETCLink Terminator box (ETC part number 7050A1024) installed in slot 1 and slot 2 of the plug-in terminal Note: Connection polarity is not important when installing the Terminator box.
Port: DMX512 input ports. Each CEM in the rack has two DMX input ports labeled port A and port B. SR12D: A twelve slot Sensor Delta dimmer rack. SR24D: A twenty-four slot Sensor Delta dimmer rack. SR48D: A forty-eight slot Sensor Delta dimmer rack.