Huawei UPS5000-A-200K-ST User Manual page 81

Hide thumbs Also See for UPS5000-A-200K-ST:
Table of Contents

Advertisement

UPS5000-A-(200 kVA-800 kVA)
User Manual
When you connect power cables, comply with the tightening torque listed in the
following table to ensure secure connections and prevent safety risks.
Table 3-10 Power cable terminal requirements
Port
Descript
ion
Mains
input
Bypass
input
Battery
input
Output
PE
Table 3-11 Recommended upstream input and downstream output circuit
breakers
UPS Capacity
300K-FT
400K
500K
600K
Issue 05 (2020-04-27)
NO TICE
Connection
Method
Crimped DT
terminal
Crimped DT
terminal
Crimped DT
terminal
Crimped DT
terminal
Crimped DT
terminal
Copyright © Huawei Digital Power Technologies Co., Ltd.
Bolt
Bolt Hole
Specifica
Diameter
tions
M16
18 mm
M16
18 mm
M16
18 mm
M16
18 mm
M12
/
Circuit Breaker Name
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
Mains input circuit breaker
Bypass input circuit breaker
Downstream output circuit
breaker
Mains input circuit breaker
3 Installation
Bolt Length Torque
50 mm
120 N·m
50 mm
120 N·m
50 mm
120 N·m
50 mm
120 N·m
35 mm
47 N·m
a
Specifications
630 A/3P
630 A/3P
630 A/3P
800 A/3P
630 A/3P
630 A/3P
1000 A/3P
800 A/3P
800 A/3P
1250 A/3P
73

Advertisement

Table of Contents
loading

Table of Contents