Step 3 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. If there is
any other alarm, you need to rectify the fault.
Step 4 View the system running diagram on the MDU to check that the UPS is working in
bypass mode.
----End
Issue 05 (2020-04-27)
NO TE
● Set the time and date correctly. Incorrect time and date will cause false fault analysis
during maintenance or repair.
● After you set network parameters, connect the UPS to the network over a network
cable, which enables you to remotely manage the UPS. If you do not need remote
management, retain the default network parameter settings.
NO TE
● If dry contact signals are connected to the system, choose System Info > Settings > Dry
contacts Set and check that the connected dry contacts have been enabled and that the
disconnected dry contacts have been disabled.
● If the system has connected to the remote EPO switch, you need to choose Monitoring
> UPS System > Running Parameter > System Settings on the WebUI and check that
EPO detection is set to Enable.