Step 10 Insert the cable terminals in the bypass cabinet into the corresponding ports on
the system signal interface board in power cabinet 1. The system signal interface
board is located at the rear of power cabinet 1. It can be seen if the cabinet rear
cover is removed.
● Cut off the cable ties binding the cables to be connected in the bypass cabinet.
● After the cables have been connected, bind the cables to the column of the
The port silk screens on the system signal interface board in power cabinet 1 are
shown in
and the ports on the system signal interface board is listed in
3-40
Issue 05 (2020-04-27)
Figure 3-38 Installing the soft copper bars numbered 52
NO TICE
When connecting the cables of the bypass cabinet to power cabinet 1, route
the cables from the internal side of the column to the system signal interface
board of power cabinet 1 so that the rear panels can be reinstalled on the
bypass cabinet and power cabinet 1.
bypass cabinet and the binding holes on the system signal interface board.
Verify that the cables are correctly connected and reinstall the rear panels.
Figure
3-39. The mapping between the cables in the bypass cabinets
shows cable connections for combined cabinets.
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
Table
3-16.
Figure
99