Huawei UPS5000-A-200K-ST User Manual page 172

Hide thumbs Also See for UPS5000-A-200K-ST:
Table of Contents

Advertisement

UPS5000-A-(200 kVA-800 kVA)
User Manual
Step 4 Remove the copper bars between the mains and bypass input wiring terminals.
(Perform this step only when the mains input and bypass input use different
power sources.)
● Properly keep the removed copper bars and bolts.
● (Optional) If copper bar protective covers are installed for the bypass cabinet, remove the
Figure 3-130 Removing the copper bar protective covers at the rear
Issue 05 (2020-04-27)
NO TE
protective covers and then the connecting copper bars. The protective covers need to be
reinstalled after the connecting copper bars are removed.
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
164