Do not bind signal cables and power cables together.
Figure 3-164 Signal cables routed from the bottom
----End
Follow-up Procedure

3.2.15 Remote EPO

● Huawei does not provide the EPO switch or cable. If the cable is required, the
● Equip the EPO switch with a protective cover to prevent misoperations, and
● Triggering EPO will shut down the rectifier, inverter, charger, and static bypass,
Issue 05 (2020-04-27)
NO TICE
After connecting cables, reinstall the covers of the power distribution subrack,
rear panel, and side panel of the bypass cabinet.
After connecting cables, check that a certain clearance is reserved between
the internal switch (if any) extension pole and power cables to avoid friction.
NO TICE
recommended cable is 22 AWG.
cover the cable with protective tubing.
but does not disconnect the UPS mains input. To power off the UPS completely,
open the front-end input switch when triggering EPO.